Bussmann® FRN-R-12 Fusetron™ FRN-R Current Limiting Time Delay Fuse, 12 A, 250 VAC/125 VDC, 200/20 kA Interrupt, Class RK5

Class RK5 Fuses
5097 MFG #: FRN-R-12
Bussmann
15.82000 / ea
  • Alternate Catalog Number: FRN-R-12
  • Application: Ind Facilities & Factories - Facility: Safety and Security Systems
  • ARRA Compliant: C
  • Buy American Compliant: C
  • Catalog Number: FRN-R-12
  • Connection: Ferrule end x ferrule end
  • Country of Origin: MX
  • Currency: USD
  • Element: Dual
  • EU RoHS Indicator: C
  • Gross Weight Per Pack: 0.0500 lb
  • Gross Weight per Pack Metric: 0.02
  • Gross Weight UOM Metric: kg
  • Harmonization Tariff Schedule Code: 8536100040
  • Height: 2.00 in
  • Height [Metric]: 5.0800 cm
  • Length: 3.00 in
  • Length [Metric]: 7.6200 cm
  • Response Time: 10 S at 500%
  • Size: 0.56 In Diameter X 2.00 In Length
  • Standard: CE Marked
  • Standards: ARRA CompliantBuy American Act CompliantRoHS CompliantCE CertifiedUL 248-12 File No. E4273 Guide JDDZCSA File No. 53787 C22.2 No. 248.12 Class 1422-02
  • Sub Brand: Bussmann Series
  • Type: Fuse
  • UNSPSC: 39121606
  • UPC 11: 05171250729
  • UPC 12: 051712507295
  • Width: 0.81 in
  • Width [Metric]: 2.0574 cm
  • Stock Status: NONSTOCK
  • Brand: Bussmann
  • Manufacturer: Eaton
  • Amperage Rating: 12 A
  • Class: RK-5
  • Interrupt Rating: 20 kAIC at 125 Vdc200 kAIC at 250 Vac
  • Voltage Rating: 250/125 VAC//VDC
EATON Bussmann series advanced protection, energy efficient FRN-R Class RK5 dual element, current- limiting time-delay fuses with optional open fuse indication on select ratings. Time-delay - 10 seconds (minimum) at 500% of rated current.
QTY
  • Applications
  • Features
Ind Facilities & Factories - Facility: Safety and Security Systems
Provides motor overload, ground fault and short circuit protection
Helps protect motors against burnout from overloads
Helps protect motors against burnout from single phasing on 3-phase systems
Simplifies and improves blackout prevention (selective coordination ratios)
Dual element fuses can be applied in circuits subject to temporary motor overloads and surge currents to provide both high performance short circuit and overload protection
The overload element provides protection against low level over current of overloads and will hold an overload which is five times greater than the amperage rating of the fuse for a minimum of 10 sec
200 kA Vac RMS Symmetrical, 20 kA at 125 Vdc