Bussmann® FRN-R-80 Fusetron™ FRN-R Current Limiting Time Delay Fuse, 80 A, 250 VAC, 200 kA Interrupt, Class RK5, Cartridge Body

Class RK5 Fuses
5101 MFG #: FRN-R-80
Bussmann
45.24000 / ea
  • Alternate Catalog Number: FRN-R-80
  • Application: Ind Facilities & Factories - Facility: Safety and Security Systems
  • ARRA Compliant: C
  • Body Size: 1.06 in Dia x 5.88 in L
  • Buy American Compliant: C
  • Catalog Number: FRN-R-80
  • Connection: Blade end x blade end
  • Country of Origin: MX
  • Currency: USD
  • Element: Dual
  • EU RoHS Indicator: C
  • Gross Weight Per Pack: 0.3000 lb
  • Gross Weight per Pack Metric: 0.14
  • Gross Weight UOM Metric: kg
  • Harmonization Tariff Schedule Code: 8536100040
  • Height: 1.00 in
  • Height [Metric]: 2.5400 cm
  • Length: 6.00 in
  • Length [Metric]: 15.2400 cm
  • Material: Fiberglass
  • Mounting Type: Holder
  • Response Time: 10 S at 500%
  • Series: FRN-R
  • Size: 1.06 In Diameter X 5.88 In Length
  • Standard: CE Marked
  • Standards: ARRA CompliantBuy American Act CompliantRoHS CompliantUL 248-12 File No. E4273 Guide JDDZCSA File No. 53787 C22.2 No. 248.12 Class 1422-02CE Certified
  • Sub Brand: Bussmann Series
  • Terminal Type: Knife Blade
  • Type: Fuse
  • UNSPSC: 39121606
  • UPC 11: 05171250741
  • UPC 12: 051712507417
  • Width: 1.00 in
  • Width [Metric]: 2.5400 cm
  • Stock Status: NORMALLY STOCKED
  • Brand: Bussmann
  • Manufacturer: Eaton
  • Amperage Rating: 80 A
  • Class: RK-5
  • Interrupt Rating: 200 kAIC at 250 Vac20 kAIC at 125 Vdc
  • Voltage Rating: 250/125 VAC//VDC
Fusetron fuses are on average 23% more energy efficient than the next leading brand.
QTY
  • Applications
  • Features
Ind Facilities & Factories - Facility: Safety and Security Systems
Provides motor overload, ground fault and short circuit protection
Helps protect motors against burnout from overloads
Helps protect motors against burnout from single phasing on 3-phase systems
Simplifies and improves blackout prevention (selective coordination ratios)
Dual element fuses can be applied in circuits subject to temporary motor overloads and surge currents to provide both high performance short circuit and overload protection
The overload element provides protection against low level over current of overloads and will hold an overload which is five times greater than the amperage rating of the fuse for a minimum of 10 sec