Bussmann® FRS-R-50ID FUSETRON DUAL-ELEME
Class RK5 Fuses
989611
MFG #: FRS-R-50ID
Bussmann
79.35000
/ ea
- Alternate Catalog Number: FRS-R-50ID
- Application: Ind Facilities & Factories - Facility: Safety and Security Systems
- ARRA Compliant: C
- Buy American Compliant: C
- Catalog Number: FRS-R-50ID
- Connection: Ferrule end x ferrule end
- Country of Origin: MX
- Currency: USD
- Element: Dual
- EU RoHS Indicator: C
- Gross Weight Per Pack: 0.2500 lb
- Gross Weight per Pack Metric: 0.11
- Gross Weight UOM Metric: kg
- Harmonization Tariff Schedule Code: 8536100040
- Height: 5.49 in
- Height [Metric]: 13.9446 cm
- Length: 5.00 in
- Length [Metric]: 12.7000 cm
- Response Time: 10 S at 500%
- Size: 1.06 In Diameter X 5.50 In Length
- Standard: CE Marked
- Standards: ARRA CompliantBuy American Act CompliantRoHS CompliantUL 248-12 Guide No. JDDZ File No. E4273CE CertifiedCSA C22.2 No. 248.12Class 1422-01 File No. 53787
- Sub Brand: Bussmann Series
- Type: Fuse
- UNSPSC: 39121606
- UPC 11: 05171220465
- UPC 12: 051712204651
- Width: 1.60 in
- Width [Metric]: 4.0640 cm
- Stock Status: NONSTOCK
- Brand: Bussmann
- Manufacturer: Eaton
- Amperage Rating: 50 A
- Class: RK-5
- Interrupt Rating: 20 kAIC at 250 Vdc200 kAIC at 600 Vac
- Voltage Rating: 600//250 VAC//VDC
Time-delay affords the same excellent overload protection as low peak fuses of motors and other type loads and circuits having temporary inrush currents such as those caused by transformers and solenoids. (In such circuits, Limitron fuses can only provide short circuit protection). Fusetron fuses are not as Fast-Acting on short circuits as low peak fuses and therefore cannot give as high a degree of component short circuit protection. Like the low peak fuse, Fusetron fuses permit the use of smaller size and less costly switches. Fusetron fuses fit rejection type fuse holders and can also be installed in holders for Class H fuses. They can physically and electrically replace Class H, K5, and other Class RK5 fuses.
- Catalog URL - IDW_DOCUMENT_c85790299cf54e7461bd1f247fc23e8817bf201e0cbc9266bf262bd79c0a3cd8.pdf(Catalog URL)
- http://www.bussmann.com(Seller Home Page URL)
- Spec Sheet 1 URL - Bussmann_FRS_R_50ID_Specification_Sheet-1.pdf(Spec Sheet 1 URL)
- Spec Sheet 2 URL - Bussmann_FRS_R_10ID_Specification_Sheet-2.pdf(Spec Sheet 2 URL)
- Spec Sheet URL - 10973_1KV2FHPCNT64A7LX.pdf(Spec Sheet URL)
- Tech Bulletin URL - bus-ele-ds-1017-frs-r-1-10-60a.pdf(Tech Bulletin URL)
- Tech Drawing URL - Bus_Ele_DS_1017_FRS-R(1-10-60)A.pdf(Tech Drawing URL)
- Video - https://www.youtube.com/embed/YMvqUyoETXk(Video)
- Applications
- Features
Ind Facilities & Factories - Facility: Safety and Security Systems |
With open fuse indication |
Dual-element fuses can be applied in circuits subject to temporary motor overloads and surge currents to provide both high performance short circuit and overload protection |
Offers a 10 sec time delay at 5 times the rated current |
The time-delay feature makes it possible to use fuse amp ratings that are much smaller than those of non-time delay fuses |
Provides current limitation to help protect downstream components from high fault currents |
Gives motor running back-up protection to motors without extra costs |
Provides a higher deg of short circuit protection (greater current limitation) in circuits in which surge currents or temporary overloads occur |