Telemecanique XMLR016G1N25 XMLR Series Fixed Differential, Pressure Sensor sensing, 5 to 10 ms response, Solid State/PNP output, 24 VDC

Pressure Sensors
PDW~11800606 MFG #: XMLR016G1N25
Telemecanique Sensors
493.50000 / ea
  • Alternate Catalog Number: XMLR016G1N25
  • ARRA Compliant: N
  • Brand: Telemecanique Sensors
  • Buy American Compliant: N
  • Catalog Number: XMLR016G1N25
  • Country of Origin: CH
  • Currency: USD
  • EU RoHS Indicator: Y
  • Gross Volume Per Pack: 61.02
  • Gross Volume per Pack Metric: 1000.00
  • Gross Volume UOM: CI
  • Gross Volume UOM Metric: cm3
  • Gross Weight Per Pack: 0.4000 lb
  • Gross Weight per Pack Metric: 181.00
  • Gross Weight UOM Metric: g
  • Harmonization Tariff Schedule Code: 9032200000
  • Item Group: 21551
  • Length [Metric]: 12.7000 cm
  • Manufacturer: Telemecanique Sensors
  • Material Composition Declaration: https://checkaproduct.se.com/DistantRequestDispatcher.aspx?action=export&pid=347330656&lang=en-us
  • Returnable: N
  • Type: Pressure transmitter;Electronic pressure sensors
  • UNSPSC: 41111927
Telemecanique XMLR016G1N25, Fixed Differential, XMLR Series, Pressure Sensor Sensing Method, 5 to 10 ms Response, Solid State/PNP Output, 24 VDC, 50 mA, Male connector Connection, (1) Yellow LED Light Source, 232.06 psi Pressure, 3.66 in H x 1.61 in W x 1.65 in D Size, IP65/IP67 Enclosure, -20 to 80 deg C Operating, Environmental Conditions: -40 to 176
QTY
  • Features
Polyester front material
0.5 kV DC uimp rated impulse withstand voltage
Fresh water 32 to 176 deg F (0 to 80 deg C))Air -4 to 176 deg F (-20 to 80 deg C))Hydraulic oil -4 to 176 deg F (-20 to 80 deg C))Refrigeration fluid -4 to 176 deg F (-20 to 80 deg C)) controlled fluid
18.6 to 232 psi (128.24 to 1599.58 kPa)18.56 to 2326 psi (1.28 to 16 bar)0.128 to 1.6 MPa adjustable range of switching point on rising pressure
6.96 psi (48 kPa)6.96 psi (0.48 bar)7 psi (48.26 kPa) minimum differential travel
Polyacrylamide 316L stainless steel housing material
Any position, but disposals can falsified the measurement in case of upside down mounting operating position
Overload protection, Reverse polarity, Overvoltage protection, Short-circuit protection type
0 to 50 s in steps of 1 second switching output time delay
Fast 50 msNormal 200 msSlow 600 ms display response time type
Fast 50 msNormal 200 msSlow 600 ms display response time type
300 ms maximum delay first up
<= 1 % of the measuring range overall accuracy
<= 0.5 % of the measuring range linearity error on analogue output
<= 0.2 % of the measuring range hysteresis on analogue output
<= 0.6 % of the measuring range measurement accuracy on switching output
+/- 03 % of measuring range/ deg C drift of the sensitivity
+/- 0.1 % of measuring range/ deg C drift of the zero point
<= 1 % of the measuring range display accuracy