Telemecanique XMLR025G2N06 XMLR Series Fixed Differential, Pressure Sensor sensing, 5 ms response, Solid State/PNP output, 24 VDC

Pressure Sensors
PDW~13604142 MFG #: XMLR025G2N06
Telemecanique Sensors
668.25000 / ea
  • Alternate Catalog Number: XMLR025G2N06
  • ARRA Compliant: N
  • Brand: Telemecanique Sensors
  • Buy American Compliant: N
  • Catalog Number: XMLR025G2N06
  • Country of Origin: CH
  • Currency: USD
  • EU RoHS Indicator: Y
  • Gross Volume Per Pack: 81.79
  • Gross Volume per Pack Metric: 1340.29
  • Gross Volume UOM: CI
  • Gross Volume UOM Metric: cm3
  • Gross Weight Per Pack: 0.4000 lb
  • Gross Weight per Pack Metric: 181.00
  • Gross Weight UOM Metric: g
  • Harmonization Tariff Schedule Code: 9032200000
  • Length [Metric]: 12.7000 cm
  • Manufacturer: Telemecanique Sensors
  • Material Composition Declaration: https://checkaproduct.se.com/DistantRequestDispatcher.aspx?action=export&pid=347330676&lang=en-us
  • Returnable: N
  • Type: Pressure transmitter;Electronic pressure sensors
  • UNSPSC: 41111927
Telemecanique XMLR025G2N06, Fixed Differential, XMLR Series, Pressure Sensor Sensing Method, 5 ms Response, Solid State/PNP Output, 24 VDC, 50 mA, Male connector Connection, (2) Yellow LED Light Source, 362.59 psi Pressure, 3.94 in H x 1.61 in W x 1.65 in D Size, IP65/IP67 Enclosure, -20 to 80 deg C Operating, Environmental Conditions: -40 to 176
QTY
  • Features
Polyester front material
0.5 kV DC uimp rated impulse withstand voltage
Fresh water 32 to 176 deg F (0 to 80 deg C))Air -4 to 176 deg F (-20 to 80 deg C))Hydraulic oil -4 to 176 deg F (-20 to 80 deg C))Refrigeration fluid -4 to 176 deg F (-20 to 80 deg C)) controlled fluid
0.2 to 2.5 MPa291 to 362.59 psi (2 to 25 bar)29 to 362 psi (199.95 to 2495.90 kPa) adjustable range of switching point on rising pressure
10.88 psi (0.75 bar)10.9 psi (75.15 kPa)10.88 psi (75 kPa) minimum differential travel
Polyacrylamide 316L stainless steel housing material
Any position, but disposals can falsified the measurement in case of upside down mounting operating position
Overload protection, Reverse polarity, Overvoltage protection, Short-circuit protection type
0 to 50 s in steps of 1 second switching output time delay
Fast 50 msNormal 200 msSlow 600 ms display response time type
Fast 50 msNormal 200 msSlow 600 ms display response time type
300 ms maximum delay first up
<= 1 % of the measuring range overall accuracy
<= 0.6 % of the measuring range measurement accuracy on switching output
+/- 03 % of measuring range/ deg C drift of the sensitivity
+/- 0.1 % of measuring range/ deg C drift of the zero point
<= 1 % of the measuring range display accuracy
10000000 cycles mechanical durability