Telemecanique XMLR2D5G2P05 XMLE,XMLF,XMLG Series Fixed differential, 5 ms response, Discrete output, 24 VDC

Pressure Sensors
PDW~11800672 MFG #: XMLR2D5G2P05
Telemecanique Sensors
297.00000 / ea
  • Alternate Catalog Number: XMLR2D5G2P05
  • Application: For accurate pressure measurement and display
  • ARRA Compliant: N
  • Buy American Compliant: N
  • Catalog Number: XMLR2D5G2P05
  • Connection: Male connector M12, 4 pins
  • Country of Origin: CH
  • Currency: USD
  • EU RoHS Indicator: Y
  • Gross Volume Per Pack: 83.72
  • Gross Volume per Pack Metric: 1371.92
  • Gross Volume UOM: CI
  • Gross Volume UOM Metric: cm3
  • Gross Weight Per Pack: 0.4100 lb
  • Gross Weight per Pack Metric: 188.00
  • Gross Weight UOM Metric: g
  • Harmonization Tariff Schedule Code: 9032200000
  • Height: 6.5000 in
  • Height [Metric]: 6.5000 cm
  • Item Group: 21551
  • Length: 13.0000 in
  • Length [Metric]: 13.0000 cm
  • Material Composition Declaration: https://checkaproduct.se.com/DistantRequestDispatcher.aspx?action=export&pid=347330757&lang=en-us
  • Output: Discrete;Solid state PNP, 2 NO/NC programmable
  • Returnable: N
  • Substitute Product Catalog Number: XZCP1241L2
  • Type: Pressure transmitter;Electronic pressure sensors
  • UNSPSC: 41111927
  • Width: 7.5000 in
  • Width [Metric]: 7.5000 cm
  • Brand: Telemecanique Sensors
  • Manufacturer: Telemecanique Sensors
  • Voltage Rating: 24 V DC SELV 17-33 V)
Telemecanique XMLR2D5G2P05, Fixed differential, XMLE,XMLF,XMLG Series, 5 ms Response, Discrete Output, 24 VDC, 250 mA, Male Connector Connection, (2) Yellow LED Light Source, 36 psi Pressure, IP65 Enclosure, -20 to 80 deg C Operating, Environmental Conditions: -40 to 176 deg F Storage Temperature
QTY
  • Applications
  • Features
For accurate pressure measurement and display
Fresh water 32 to 176 deg F (0 to 80 deg C))Air -4 to 176 deg F (-20 to 80 deg C))Hydraulic oil -4 to 176 deg F (-20 to 80 deg C))Refrigeration fluid -4 to 176 deg F (-20 to 80 deg C)) controlled fluid
2.90 to 36.26 psi (20 to 250 kPa)2.9 to 36.2 psi (19.99 to 249.59 kPa)2.90 to 36.26 psi (0.2 to 2.5 bar) adjustable range of switching point on rising pressure
1.89 to 35.10 psi (13 to 242 kPa)1.89 to 35.10 psi (0.13 to 2.42 bar)1.81 to 35.2 psi (12.48 to 242.70 kPa) adjustable range of switching point on falling pressure
1.1 psi (7.58 kPa)1.16 psi (8 kPa)1.16 psi (08 bar) minimum differential travel
316L stainless steelPolyacrylamide housing material
Any position, but disposals can falsified the measurement in case of upside down mounting operating position
Overload protection, Reverse polarity, Overvoltage protection, Short-circuit protection type
0 to 50 s in steps of 1 second switching output time delay
4 digits 7 segments display type
300 ms maximum delay first up
300 ms maximum delay first up
<= 1 % of the measuring range overall accuracy
<= 0.6 % of the measuring range measurement accuracy on switching output
+/- 03 % of measuring range/ deg C drift of the sensitivity
+/- 0.1 % of measuring range/ deg C drift of the zero point
<= 1 % of the measuring range display accuracy
10000000 cycles mechanical durability
0.5 kV DC uimp rated impulse withstand voltage